LTDS Table 4 Fault Level
Dataset description:
The Long-Term Development Statement (LTDS) provides essential information to assist current and prospective users of National Grid Electricity Distribution’s (NGED) network in identifying...
Source: LTDS Tabular Model
Data Dictionary
| Title | Type | Label | Description | Example |
|---|---|---|---|---|
| Licence | text | Licence area for data |
EMIDS | |
| GSP Group | text | Berkswell 132kV | ||
| Substation or Busbar Name | text | Berkswell 275/132kV | ||
| Node A | text | Busbar code |
BESW1_&405 | |
| Node B | text | Busbar code |
BESW1_MAIN2 | |
| Branch ID | text | Identifier for branch between Node A and Node B |
*1 | |
| Status | text | New, Removed or Unchanged |
Updated | |
| Operating Voltage | numeric | kV | 132 | |
| R1 | numeric | % on 100MVA Base | System Impedance |
0.0013 |
| X1 | numeric | % on 100MVA Base | System Impedance |
0.0302 |
| 3ph Peak Make | numeric | kA | Existing System Fault Current |
42.02598 |
| 1ph Peak Make | numeric | kA | Existing System Fault Current |
54.29236 |
| 3ph RMS Break | numeric | kA | Existing System Fault Current |
15.04723 |
| 1ph RMS Break | numeric | kA | Existing System Fault Current |
20.44929 |
| 3ph Peak Make Rating | numeric | kA | Rating |
39.03675 |
| 1ph Peak Make Rating | text | kA | Rating |
39.03675 |
| 3ph RMS Break Rating | text | kA | Rating |
15.30853 |
| 1ph RMS Break Rating | text | kA | Rating |
15.30853 |